PRODUCT CENTER
CONTACT US
Preformed Guying Tension Set
Compenent Illustration
① Twisted ring: Furnished as standard, all sizes
② Installation / identifying color code
(A) indicate starting point for application on smaller diameter ?ttings described on the reverse side of this page.
(B) Indicates alternate starting point for application on large diameter
?ttings described on the reverse side of this page.
③ Pitch length: One complete wrap
④ Label:shows catalog number, nominal sizes
⑤ / ⑥ Long/short leg: Identi?es rods belonging to each leg, after application.
*During application, the short leg should be applied ?rst
Application
The set is suitable to the ?xing of pole in distribution line.
Material
The set is made of the same basic material as the strand to which they are applied, including galvanized steel, copperweld, aluminumweld steel, stainless type 302,306.
Attention
1) Within the first 3 months safter initial application,it may be removed and reapplied two times after initial application for the purpose of retensioning the guy. After 3 months a new dead-end should be used any time removal is required.
2) It should be used on hardware that is held in a ?xed position;the ?tting should not be allowed to rotate or spin about the axis of the strand. The should not be used as tools.
3) Lay directions should be the same;
4) For the consideration of appearance and safety, the end should be cut close to mark. If possible, it should be hided in the tube of marks. If necessary, the end could extend over the ring for ground. Any end over 51mm should be bundled up to avoid dispersing ;
5) This set is not suitable to the insulator which inside hole is squareness.
Fitting
Drawing 3-2 thimble ring (table 3-1)
Model table